5 reasons a warehouse with roof fans still runs hot.

5 reasons a warehouse with roof fans still runs hot.

Share Article

Roof fans are the right answer to warehouse heat, which is why it’s frustrating when a building that has them still runs hot through summer. The equipment is rarely the problem. Extraction underperforms for reasons that sit around the fan rather than in it, and most of them can be identified in one walk of the building.

Overview. 

  • No inlet path: a fan in a sealed building moves a fraction of its rated airflow. 
  • Even spacing, uneven heat: fans spread across a roof rather than placed over where heat is generated. 
  • Circulation mistaken for extraction: moving hot air around a building isn’t removing it. 
  • No overnight purge: a building that doesn’t clear starts each day higher than the last. 
  • Solar gain treated as process heat: two different loads needing two different responses.

1. There’s no inlet path for replacement air.

An exhaust fan has to draw air from somewhere. In a tightly sealed warehouse it works against pressure and moves a fraction of its rating while sounding and looking exactly like a fan performing correctly. 

This is the most common cause and the least visible one, because nothing about the installation appears wrong. Adding capacity doesn’t fix it either, since increasing fan capacity doesn’t improve ventilation where the system has excessive resistance or insufficient replacement air. After removing their previous extraction system, one manufacturer found airflow inadequate through summer. Fanquip installed two 800mm filtered roof supply fans positioned over the high-heat areas, set out in heat extraction fans for summer-ready manufacturing. 

2. The fans are evenly spaced and the heat isn’t.

Roof fans often get distributed across a roof on a grid, which looks orderly and ignores where the heat actually comes from. 

Process equipment, packing lines, battery charging bays and loading docks all generate heat at specific points. A fan over an empty aisle extracts warm air; a fan over the heat source extracts hot air, and moves more energy out of the building for the same running cost. In most warehouses, position is worth checking before capacity.

3. Circulation is being asked to do extraction’s job. 

Giant fans and air circulators are frequently installed as the heat response, and they do something useful, but it isn’t removal. 

A circulator redistributes air within a space. An extraction fan removes it from the building. In a warehouse holding accumulated heat, circulation makes conditions feel better at floor level while the total heat load stays where it was. The two work together, with circulation moving air toward the extraction point and extraction taking it out, which extraction fan vs exhaust fan sets out in more detail.

4. The building never purges overnight. 

Warehouse heat accumulates across a run of hot days rather than peaking on the hottest one. 

A building that holds heat overnight starts the next morning warmer than it started the previous one, and by the third or fourth day of a heatwave the internal temperature bears little relationship to the forecast maximum. Extraction running only during occupied hours misses the period when outside air is coolest and the temperature difference is doing the most work. 

5. Solar gain is being treated as process heat.

Fanquip’s own breakdown of heat sources separates machinery and process heat from solar and seasonal heat, and the distinction matters for where extraction goes. 

Solar gain loads the roof plane across the day, which suits distributed high-level extraction. Process heat rises from identifiable points, which suits extraction placed above those points. A warehouse carrying both needs both, and sizing against only one leaves a gap that shows up in the afternoon. The operational impact of heat build-up in large facilities covers how different heat sources call for different approaches.

What to check before adding capacity. 

Most of these can be answered in one pass of the building on a warm afternoon. 

  • Inlet path. Whether air has a controlled way in, or the fans are pulling against a sealed envelope. 
  • Fan position. Where the fans sit relative to where heat is generated. 
  • Equipment type. Whether the fans installed extract from the building or circulate within it. 
  • Run schedule. Whether extraction runs overnight or stops with the shift. 
  • Heat source. Whether the load is solar, process, or both. 

Adding fans before checking these usually adds running cost without adding extraction.

Matching the equipment to the problem.   

Removing accumulated heat at roof level. Vertical discharge roof fans discharge upward to stop hot air recirculating back onto the roof, in hot dip galvanised steel with a butterfly damper against rain ingress. Curb base and profile base hooded roof fans do the same job at a lower profile where the roof structure suits it. 

Bringing clean replacement air in. Filtered roof supply fans deliver filtered air through the roof, which suits buildings where ceiling height leaves no room for conventional filter boxes. 

Moving air toward the extraction point. Giant fans cover 490 to 1,300 m² depending on diameter, moving high volumes at low speed without creating a draught. Air circulators handle targeted movement in smaller zones. Both extend airflow past racking and partitions so the extraction has something to draw on, covered in how industrial air circulators improve airflow coverage.

The full range sits under Fanquip’s warehouse ventilation.

Heat removal is a system, not a fan count.   

A warehouse that runs hot with roof fans installed usually has an extraction system doing one job well and two others not at all. The fix is rarely more capacity, and it is frequently a supply path, a repositioned unit or a run schedule that covers the hours when outside air is coolest. 

Working out which one applies starts with looking at the building rather than the equipment list. Talk to Fanquip’s team about an assessment before the first run of hot days.

FAQs 

How do you get heat out of a warehouse in summer? 

Extract it at roof level where it accumulates, give the extraction a controlled inlet for replacement air, and position the fans over where the heat is generated rather than evenly across the roof. Circulation fans move air toward the extraction point but don’t remove heat from the building. 

Why is my warehouse still hot with roof fans installed?

The most common cause is no path for replacement air. A sealed building leaves the fan working against pressure, moving a fraction of its rated airflow while appearing to run normally.

Do more roof fans fix a hot warehouse? 

Not usually. Increasing fan capacity doesn’t improve ventilation if the system has excessive resistance or insufficient replacement air, so the inlet path is worth checking before adding units. 
 

What’s the difference between a roof fan and a giant fan for warehouse heat? 

A roof fan removes air from the building. A giant fan or air circulator redistributes air within it. Both have a role, but only extraction reduces the total heat held in the space. 

Should warehouse extraction run overnight in summer? 

Running during the coolest part of the day uses the largest temperature difference, and it stops heat carrying over into the next morning across a run of hot days. 

What type of roof fan suits a warehouse? 

Vertical discharge roof fans prevent discharged air recirculating back into the building. Curb base and profile base hooded fans suit lower-profile installations.

Stay up to date

Stay up to date with the latest sales, service tips and news. Discover the complete Fanquip product range via our catalogue, with industrial cooling, heating, filtration, and ventilation solutions across a wide range of industries. Refer to our industrial guides for insights into common ventilation issues and solutions provided by Fanquip.